Application In door installations, in cable ducts, outdoor and underground for power stations, industrial plants and switching stations as well as local supply systems if increased protection is necessary. In case of mechanical damage the screen prevents any demage due to power leak to the surrounding area.
Construction Conductor: Aluminium cector shape conductor
Insulation: Polyvinylchloride (PVC)
Filling: Core covering
Armour: Concentric copper wire, copper tape as binder, polyester tape
Outer Sheath: Polyvinylchloride (PVC)
Standards OVE/ONORM E 8200-603, HD 603 S1, IEC 60502 - 1
EN 60228 class 1, 2
Rated voltage 600/1000 V
Test Voltage (AC) 4 kV
Max. short circuit temperature 160°C (max. 5 sec.)
Bending Radius 15D
Temperature Range -5°C till +70°C
Flame spread resistance EN 60332-1-2
CPR class Eca