Application Safety cables are used in all locations where a high degree of protection against fireand fire-damage has to be provided for human life and equipment and are, therefore, subject to high security requirements. These cables may be used indoors and outdoors. They may not be installed directly into the ground and into the water. This cable conforms to Safety Class II standards
Construction Conductor: Solid (RE) or stranded (RM/SM) bare cooper
Insulation: Halogen - free, crosslinked polyethylene
Filling: Core covering of a halogen-free compound
Outer Sheath: Halogen Free Flame Retardant (HFFR), Black
Standards VDE 0276-604 5G, HD 604 S1
EN 60228 class 1, 2
HD 308 S2 (core colours)
EN 61034-2, EN 60754-2
Rated voltage 600/1000 V
Test Voltage (AC) 4 kV
Max. short circuit temperature 250°C (max. 5 sec.)
Bending Radius 12D
Temperature Range -40°C till +90°C
Flame spread resistance EN 60332-1-2
EN 60332-3-24
CPR class Eca